RE-2Y(St)HSWAH-TIMF&RE-2X(St)HSWAH-TIMF
HALOGEN-FREE INSTRUMENTATION CABLES, Acc. to BS 5308 PART 1 TYPE 2RE-2Y(St)HSWAH-TIMF,SİNGLE & MULTİ-TRIPLE, PE INSULATED, INDIVIDUAL & COLLECTİVE SCREENED, ARMOUR, LSZH SHEATHEDRE-2X(St)HSWAH-TIMF,SİNGLE & MULTİ-TRIPLE, XLPE INSULATED, INDIVIDUAL & COLLECTİVE SCREENED,ARMOUR, LSZH SHEATHED
These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire. With blue sheath it is suitable for intrinsically safe systems. The armour above the inner sheath protects the cable from mechanical shocks. These cables are recommended for direct burial. They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.
Conductor: Plain annealed copper wire, BS 6360, 0,50 mm2 and 1,0 mm2 solid, 0,50 mm2 and, 0,75 mm2 flexible or 1,5 mm2 stranded
Insulation (2Y): PE compound, BS 6234 Type03 (RE-2Y….)
Insulation (2X): XLPE compound, GP8, BS 7655 (RE-2X….)
Core identification: Black / White / Red; with numbered tape under, separator tape of the pair screen, *Upon request ; Black / White / Red cores numbered 1-1-1, 2-2-2,…
Triple: Three conductors twisted to a triple
TIMF Construction: Polyester tape above the triple, AL-PES tape, over tinned copper drain wire, 0,50 mm2
Lay-up: TIMF laid up in layers of optimum pitch
Separator: Polyester tape
Screen: AL-PES tape over tinned copper drain wire 0,50 mm2
Bedding: LSZH compound, Black
Armour: Galvenized round steel wire, BS EN 10257-1
Outer sheath: LSZH compound, LST1, BS 7655
Sheath colour: RAL 9005, Black or RAL 5015, Blue
Standard: Designed acc. to BS 5308 Part 1 Type 1
Insulation thickness: 0,50mm2 : 0,50mm, 1,0mm2 : 0,60mm, 0,50mm2 : 0,60mm, 0,75mm2 : 0,60mm, 1,50mm2 : 0,60mm
Conductor class, BS 6360: 0,50mm2 : Class 1, 1,0mm2 : Class 1, 0,50mm2 : Class 5, 0,75mm2 : Class 5, 1,5mm2 : Class 2
Conductor resistance: 0,50mm2 : 36,8 Ω/km, 1,0mm2 : 18,4 Ω/km, 0,50mm2 : 39,7 Ω/km, 0,75mm2 : 26,5 Ω/km, 1,5mm2 : 12,3 Ω/km
Insulation resistance: Min. 5000 MΩ.km
Mutual Capacitance: 0,50 mm2 : max. 115 pF/m, 0,75 mm2 : max. 115 pF/m, 1,0 mm2 : max. 115 pF/m, 1,5 mm2 : max. 120 pF/m
Capacitance unbalance: (1 kHz) : max. 250 pF/250 m
L / R (ratio) (max.): 0,50mm2 : 25 µH/Ω, 0,75mm2 : 25 µH/Ω, 1,0mm2 : 25 µH/Ω1,5mm2 : 40 µH/Ω
Rated voltage: 300/500V
Test voltage: Urms core-core : 1000 V, Urms core-screen : 1000 V
Temperature range (2Y): operation : - 40 oC ~ + 70 oC, ınstallation : - 5 oC ~ + 50 oC
Temperature range (2X): operation : - 40 oC ~ + 90 oC, ınstallation : - 5 oC ~ + 50 oC
Min. bending radius: 8 x D
Flame retardance test: IEC 60332-1 & BS EN 60332-1, IEC 60332-3 & BS EN 50266-2-4
Smoke density test: IEC 61034-2 & BS EN 61034-2
Halogen-free properties test: IEC60754-1/2 & BS EN 50267-2