RE-2Y(St)Y-fl-PIMF & RE-2X(St)Y-fl-PIMF
INSTRUMENTATION CABLES, EN 50288-7RE-2Y(St)Y-fl-PIMF,MULTİ-PAİR, PE INSULATED, INDIVIDUAL & COLLECTİVE SCREENED, PVC SHEATHEDRE-2X(St)Y-fl-PIMF,MULTI-PAIR, XLPE INSULATED, INDIVIDUAL & COLLECTIVE SCREENED, PVC SHEATHED
These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.
Insulation (2X): XLPE compound, EN 50290-2-29; (RE-2X….)
Core identification: Black / White ; with numbered tape under , separator tape of the pair screen, Upon request ; Black / Blue cores numbered 1-1, 2-2,…, Other core configurations manufactured upon request.
Pair: Two conductors twisted to a pair
PIMF Construction: Polyester tape above the pair, AL-PES tape, over solid tinned copper drain wire, 0,60 mm, Upon request ; Stranded 0,50 mm2 copper drain wire
Lay-up: PIMF laid up in layers of optimum pitch
Separator: Polyester tape
Screen: AL-PES tape over stranded tinned copper drain, wire 0,50 mm2
Outer sheath (2Y): PVC comp., flame retardant; EN 50290-2-22
Outer sheath (2X): PVC compound, 90 oC grade; EN 50290-2-22
Sheath colour: RAL 9005, Black or RAL 5015, Blue
Conductor: Plain copper wire, stranded, IEC 60228 Sınıf 2, TS/DIN EN 60228 Sınıf 2
Insulation (2Y): PE compound, EN 50290-2-23; (RE-2Y….)
Standard: TS/DIN EN 50288-7
Insulation thickness: 0,50mm2 : 0,40 mm, 0,75mm2 : 0,40 mm, 1,0mm2 : 0,40 mm, 1,3mm2 : 0,45 mm, 1,5mm2 : 0,45 mm
Conductor resistance: 0,50mm2 : 36,7 Ω/km, 0,75mm2 : 25,0 Ω/km, 1,0mm2 : 18,5 Ω/km, 1,3mm2 : 14,2 Ω/km, 1,5mm2 : 12,3 Ω/km
Insulation resistance: Min. 5000 MΩ.km
Mutual Capacitance: max. 120 pF/m
L / R (ratio) (max.): 0,50mm2 : 25 µH/Ω, 0,75mm2 : 25 µH/Ω, 1,0mm2 : 25 µH/Ω1,30mm2 : 40 µH/Ω, 1,5mm2 : 40 µH/Ω
Rated voltage: 300V
Test voltage: Urms core-core : 1500 V, Urms core-screen : 1500 V
Temperature range (2Y): operation : - 30 oC ~ + 70 oC, ınstallation : - 5 oC ~ + 50 oC
Temperature range (2X): operation : - 30 oC ~ + 90 oC, ınstallation : - 5 oC ~ + 50 oC
Min. bending radius: 7,5 x D
Flame retardance test: IEC 60332-1 & EN 60332-1