HISbatt All-in-One 215kWh Energystorage
Battery Systems
Battery Rack Model HIS-BATT-215-15-C05-A
Battery capacity (Installed) 215.04 kWh
Battery Module Model HIS-MOD-14-1P16S-C05-A
Battery Modules per Rack 15
Battery Cell Model CATL 280Ah
Battery Cells per Module 16
Battery cells per Rack 240
Cycles @ 90% DoD usable | 70% EoL | 6,000
Battery Management System HIS-BMS (3 Level Safety)
Inverter
Battery Inverter Model Gridsave 92.0 TL3
Nominal apparent power 92 kVA
Maximum apparent power 92 kVA
Nominal AC current (I) 132.3 A
Nominal AC voltage 400 VAC, 3 Phase
AC power frequency (range) 50 Hz (45 Hz -65 Hz)
Reactive power / cos phi 0– 100% Smax /0.30 ind. – 0.30 cap.
IGBT switching frequency 48 kHz
Inverter efficiency (Max) 98.7%
DC voltage range 600 VDC to 876 VDC
Maximum total harmonic distortion < 3% at nominal power
Inverter location Mounted on battery rack
Energy Management System
Main Controller HIS energy controller
Control software myHIS-Flow
Applications Peak shaving, PV Self-Consumption, Time of Use, EV Charging Booster, Multi Use etc.
External communication interfaces Ethernet / MODBUS TCP
Protective Devices & Certifications
Battery (DC) Fuse, and DC load break switch
DC overvoltage protection Surge arrester, type I
Ground fault monitoring Yes
Insulation monitoring Yes
Safety & Fire protection Smoke detectors, CO sensors, H2 sensors, Smoke detectors, temperature sensors, humidity sensors, water
leakage detection, Independent Fire Protection (FK5112)
Cooling principle (Inverter) Forced Air Cooled (Fans)
Cooling principle (Battery) Forced Air Cooled (HVAC)
Battery Operation Temperature: -10 C to 45 C
Battery Storage Temperature: -30 C to 50 C
BESS Protection Class IP54 (Indoor + Outdoor)
Dimensions (mm) 1200 x 1000 x 2100 (mm)
BESS weight (92kW/215kWh) 2,100 kg
Battery storage temperature range (> 1 month): 0 °C to 35 °C (30% to 50% SoC)
Safety Certifications IEC 62619, UL9540A (cell), EC 62477-1:2012,
EMC Certificates IEC 61000-6-2, IEC 61000-6-4
BESS Life (rated conditions) 20 year